MGC-96079B
Revised 08-02
Catalog Section 75
(00-02-0766)
Digital Generator Panels
FWMurphy
MGC447 and MGC547 Series
■
Microprocessor-Based Controller
■
Digital Engine and Generator Display
■
Pre-Programmed, Full Featured
■
Built-In Advanced Communications
■
MGC547
Compact Design, NEMA 1 Drip Proof
Operating Temperature: -4 to 149°F (-20 to 65°C).
Storage Temperature: -4 to 149°F (-20 to 65°C).
Relative Humidity: 95%RH @ 60°C (140°F).
Description
Features
•
Pre-programmed generator panels for typical
gen-set operations: warm-up, transfer to
load, run time, engine unload, cooldown.
The MGC447 and MGC547 generator panels
provide inexpensive engine and generator
monitoring and control with digital accuracy.
These microprocessor-based controllers
include all basic industry requirements plus
many value added features such as: remote
communications and control capabilities; on-
board real time clock; shutdown history dis-
play of last 5 shutdowns; service reminders.
Communications:
MGC447: 1-RS485 serial port.
MGC547: 2-RS485 and 2-RS232 serial ports.
•
•
For 3-phase, 4-wire or 1-phase, 3-wire generators.
Digital readout of all engine and generator
functions: pressure, temperature, rpm, amps
and volts. Monitored with first-out shutdown
annunciation.
Digital Inputs: 3 optically-isolated, (positive voltage
or ground) such as from Murphy SWICHGAGE®s.
Input 1: Auto position on toggle switch
*
Input 2: Test position on toggle switch
*
•
Built-in communication for remote start/stop
and monitoring engine and generator func-
tions (MGC547 models).
Input 3: Spare 1 Input
Operating parameters are configured through
a three-button interface. Data is displayed on a
32-character, back lit alphanumeric liquid
crystal display. Access to the system memory
is controlled by entry codes, and the program
is stored in EPROM.
Analog Inputs: 7
Analog 1: Water Temperature Sender
Analog 2: Engine Oil Pressure Sender
Analog 3: Low Coolant Input (closed on fault)
Analog 4: Oil Level Input (closed on fault)
•
•
•
Optically-isolated noise resistant inputs.
Open collector transistor outputs.
Crank and Rest cycle timers, 1 to 300 seconds
each (adjustable).
Analog 5: AC Volts (0-5 VDC)
*
These panels accept a variety of sensor inputs
such as from Murphy electric gage type resis-
tive sending units and digital inputs such as
from SWICHGAGE® instruments.
Analog 6: AC Amps (0-5 VDC)
*
•
•
Shutdown time delay, 2 to 2000 seconds
(adjustable), locks out low oil pressure
and high temperature on start-up.
Analog 7: Remote Start/Stop
Frequency Input: 1 optically-isolated for speed
reference from magnetic sensor (pickup).
Crank disconnect and overspeed sensing
operates from a magnetic pickup signal
(requires 2 Vrms minimum) or alternator
tachometer terminal.
The MGC447 and MGC547 feature open col-
lector transistor type and relay type outputs.
Outputs: 7
Output 1: Fuel Solenoid
Output 2: Starter
Output 3: Common Fail
†
†
These compact panels measure only 13-1/4 x
8-1/2 x 12-1/2 inches (337 x 216 x 318 mm), and
are shock mounted and rated NEMA 1 drip-proof.
†
Important: Off-panel items such as senders, mag-
netic sensors and CT’s must be ordered separately.
Output 4: Glow Plug**
Output 5: Generator Regulator Control**
The MGC547 Series models incorporate built-
in serial ports for advanced communication
capabilities. They can communicate with
remote terminals, such as a computer via
modem or can automatically dial your pager to
inform you of the status of the generator.
Output 6: Phase 2 Selection
*
Specifications
NOTE: These specification apply to all models
unless otherwise indicated.
Output 7: Phase 3 Selection
*
NOTE: I/O’s and comm. ports are program specific
and will vary depending upon the software program
used. Custom programming is available.
MGC447 models: EMS447 controller.
MGC547 models: EMS547 controller.
Power Requirements:
*
Internal, not for customer connection.
The user is able to start or stop the engine, view
operating parameters and reset or acknowledge
abnormal conditions from a computer.
** Open collector transistor type, 300 mA maximum.
To drive customer supplied relay.
Auxiliary relay, customer connection is
form “A” relay contact, 12 V, 40 A; 24 V, 16 A.
12 VDC battery for 12 V models.
24 VDC battery for 24 V models.
†
|
Murphy Switch AS3000 User Manual
NETGEAR Network Router D6200 100NAS User Manual
Nikon Network Card EP 6 User Manual
Niles Audio Speaker System OS6 User Manual
Oki Printer 62411601 User Manual
Omron Fitness Electronics HJ 320 E User Manual
Panasonic All in One Printer KX MC6020CX User Manual
Panasonic Electronic Accessory EE26 User Manual
Panasonic Smoke Alarm EQ 500 Series User Manual
Panasonic Telephone KX T7320 User Manual